      1 ## apcupsd.conf v1.1 ##
      2 # 
      3 #  for apcupsd release 3.14.1 (04 May 2007) - unknown
      4 #
      5 # "apcupsd" POSIX config file
      6 
      7 #
      8 # ========= General configuration parameters ============
      9 #
     10 
     11 # UPSNAME xxx
     12 #   Use this to give your UPS a name in log files and such. This
     13 #   is particularly useful if you have multiple UPSes. This does not
     14 #   set the EEPROM. It should be 8 characters or less.
     15 UPSNAME ups1
     16 
     17 # UPSCABLE <cable>
     18 #   Defines the type of cable connecting the UPS to your computer.
     19 #
     20 #   Possible generic choices for <cable> are:
     21 #     simple, smart, ether, usb
     22 #
     23 #   Or a specific cable model number may be used:
     24 #     940-0119A, 940-0127A, 940-0128A, 940-0020B,
     25 #     940-0020C, 940-0023A, 940-0024B, 940-0024C,
     26 #     940-1524C, 940-0024G, 940-0095A, 940-0095B,
     27 #     940-0095C, M-04-02-2000
     28 #
     29 UPSCABLE smart
     30 
     31 # To get apcupsd to work, in addition to defining the cable
     32 # above, you must also define a UPSTYPE, which corresponds to
     33 # the type of UPS you have (see the Description for more details).
     34 # You must also specify a DEVICE, sometimes referred to as a port.
     35 # For USB UPSes, please leave the DEVICE directive blank. For
     36 # other UPS types, you must specify an appropriate port or address.
     37 #
     38 # UPSTYPE   DEVICE           Description
     39 # apcsmart  /dev/tty**       Newer serial character device,
     40 #                            appropriate for SmartUPS models using
     41 #                            a serial cable (not USB).
     42 #
     43 # usb       <BLANK>          Most new UPSes are USB. A blank DEVICE
     44 #                            setting enables autodetection, which is
     45 #                            the best choice for most installations.
     46 #
     47 # net       hostname:port    Network link to a master apcupsd
     48 #                            through apcupsd's Network Information
     49 #                            Server. This is used if you don't have
     50 #                            a UPS directly connected to your computer.
     51 #
     52 # snmp      hostname:port:vendor:community
     53 #                            SNMP Network link to an SNMP-enabled
     54 #                            UPS device. Vendor is the MIB used by
     55 #                            the UPS device: can be "APC", "APC_NOTRAP"
     56 #                            or "RFC" where APC is the powernet MIB,
     57 #                            "APC_NOTRAP" is powernet with SNMP trap
     58 #                            catching disabled, and RFC is the IETF's 
     59 #                            rfc1628 UPS-MIB. You usually want "APC".
     60 #                            Port is usually 161. Community is usually
     61 #                            "private".
     62 #
     63 # dumb      /dev/tty**       Old serial character device for use 
     64 #                            with simple-signaling UPSes.
     65 #
     66 # pcnet    ipaddr:username:passphrase
     67 #                            PowerChute Network Shutdown protocol
     68 #                            which can be used as an alternative to SNMP
     69 #                            with AP9617 family of smart slot cards.
     70 #                            ipaddr is the IP address of the UPS mgmt
     71 #                            card. username and passphrase are the
     72 #                            credentials for which the card has been
     73 #                            configured.
     74 #
     75 UPSTYPE apcsmart
     76 DEVICE /dev/ttyS0
     77 
     78 
     79 # LOCKFILE <path to lockfile>
     80 #   Path for device lock file. Not used on Win32.
     81 LOCKFILE /var/lock
     82 
     83 # SCRIPTDIR <path to script directory>
     84 #   Directory in which apccontrol and event scripts are located.
     85 SCRIPTDIR /etc/apcupsd
     86 
     87 # PWRFAILDIR <path to powerfail directory>
     88 #   Directory in which to write the powerfail flag file. This file
     89 #   is created when apcupsd initiates a system shutdown and is
     90 #   checked in the OS halt scripts to determine if a killpower
     91 #   (turning off UPS output power) is required.
     92 PWRFAILDIR /etc
     93 
     94 # NOLOGINDIR <path to nologin directory>
     95 #   Directory in which to write the nologin file. The existence
     96 #   of this flag file tells the OS to disallow new logins.
     97 NOLOGINDIR /etc
     98 
     99 
    100 #
    101 # ======== Configuration parameters used during power failures ==========
    102 #
    103 
    104 # The ONBATTERYDELAY is the time in seconds from when a power failure
    105 #   is detected until we react to it with an onbattery event.
    106 #
    107 #   This means that, apccontrol will be called with the powerout argument
    108 #   immediately when a power failure is detected.  However, the
    109 #   onbattery argument is passed to apccontrol only after the 
    110 #   ONBATTERYDELAY time.  If you don't want to be annoyed by short
    111 #   powerfailures, make sure that apccontrol powerout does nothing
    112 #   i.e. comment out the wall.
    113 #ONBATTERYDELAY 6
    114 
    115 # 
    116 # Note: BATTERYLEVEL, MINUTES, and TIMEOUT work in conjunction, so
    117 # the first that occurs will cause the initiation of a shutdown.
    118 #
    119 
    120 # If during a power failure, the remaining battery percentage
    121 # (as reported by the UPS) is below or equal to BATTERYLEVEL, 
    122 # apcupsd will initiate a system shutdown.
    123 BATTERYLEVEL 5
    124 
    125 # If during a power failure, the remaining runtime in minutes 
    126 # (as calculated internally by the UPS) is below or equal to MINUTES,
    127 # apcupsd, will initiate a system shutdown.
    128 MINUTES 3
    129 
    130 # If during a power failure, the UPS has run on batteries for TIMEOUT
    131 # many seconds or longer, apcupsd will initiate a system shutdown.
    132 # A value of 0 disables this timer.
    133 #
    134 #  Note, if you have a Smart UPS, you will most likely want to disable
    135 #    this timer by setting it to zero. That way, you UPS will continue
    136 #    on batteries until either the % charge remaining drops to or below BATTERYLEVEL,
    137 #    or the remaining battery runtime drops to or below MINUTES.  Of course,
    138 #    if you are testing, setting this to 60 causes a quick system shutdown
    139 #    if you pull the power plug.   
    140 #  If you have an older dumb UPS, you will want to set this to less than
    141 #    the time you know you can run on batteries.
    142 TIMEOUT 0
    143 
    144 #  Time in seconds between annoying users to signoff prior to
    145 #  system shutdown. 0 disables.
    146 ANNOY 300
    147 
    148 # Initial delay after power failure before warning users to get
    149 # off the system.
    150 ANNOYDELAY 60
    151 
    152 # The condition which determines when users are prevented from
    153 # logging in during a power failure.
    154 # NOLOGON <string> [ disable | timeout | percent | minutes | always ]
    155 NOLOGON disable
    156 
    157 # If KILLDELAY is non-zero, apcupsd will continue running after a
    158 # shutdown has been requested, and after the specified time in
    159 # seconds attempt to kill the power. This is for use on systems
    160 # where apcupsd cannot regain control after a shutdown.
    161 # KILLDELAY <seconds>  0 disables
    162 KILLDELAY 0
    163 
    164 #
    165 # ==== Configuration statements for Network Information Server ====
    166 #
    167 
    168 # NETSERVER [ on | off ] on enables, off disables the network
    169 #  information server. If netstatus is on, a network information
    170 #  server process will be started for serving the STATUS and
    171 #  EVENT data over the network (used by CGI programs).
    172 NETSERVER on
    173 
    174 # NISIP <dotted notation ip address>
    175 #  IP address on which NIS server will listen for incoming connections.
    176 #  This is useful if your server is multi-homed (has more than one
    177 #  network interface and IP address). Default value is 0.0.0.0 which
    178 #  means any incoming request will be serviced. Alternatively, you can
    179 #  configure this setting to any specific IP address of your server and 
    180 #  NIS will listen for connections only on that interface. Use the
    181 #  loopback address (127.0.0.1) to accept connections only from the
    182 #  local machine.
    183 NISIP 0.0.0.0
    184 
    185 # NISPORT <port> default is 3551 as registered with the IANA
    186 #  port to use for sending STATUS and EVENTS data over the network.
    187 #  It is not used unless NETSERVER is on. If you change this port,
    188 #  you will need to change the corresponding value in the cgi directory
    189 #  and rebuild the cgi programs.
    190 NISPORT 3551
    191 
    192 # If you want the last few EVENTS to be available over the network
    193 # by the network information server, you must define an EVENTSFILE.
    194 EVENTSFILE /var/log/apcupsd.events
    195 
    196 # EVENTSFILEMAX <kilobytes>
    197 #  By default, the size of the EVENTSFILE will be not be allowed to exceed
    198 #  10 kilobytes.  When the file grows beyond this limit, older EVENTS will
    199 #  be removed from the beginning of the file (first in first out).  The
    200 #  parameter EVENTSFILEMAX can be set to a different kilobyte value, or set
    201 #  to zero to allow the EVENTSFILE to grow without limit.
    202 EVENTSFILEMAX 10
    203 
    204 #
    205 # ========== Configuration statements used if sharing =============
    206 #            a UPS with more than one machine
    207 
    208 # NETTIME <int>
    209 #   Interval (in seconds) at which the NIS client polls the server.
    210 #   Used only when this apcupsd is a network client (UPSTYPE net).
    211 #NETTIME 60
    212 
    213 #
    214 # Remaining items are for ShareUPS (APC expansion card) ONLY
    215 #
    216 
    217 # UPSCLASS [ standalone | shareslave | sharemaster ]
    218 #   Normally standalone unless you share an UPS using an APC ShareUPS
    219 #   card.
    220 UPSCLASS standalone
    221 
    222 # UPSMODE [ disable | share ]
    223 #   Normally disable unless you share an UPS using an APC ShareUPS card.
    224 UPSMODE disable
    225 
    226 #
    227 # ===== Configuration statements to control apcupsd system logging ========
    228 #
    229 
    230 # Time interval in seconds between writing the STATUS file; 0 disables
    231 STATTIME 0
    232 
    233 # Location of STATUS file (written to only if STATTIME is non-zero)
    234 STATFILE /var/log/apcupsd.status
    235 
    236 # LOGSTATS [ on | off ] on enables, off disables
    237 # Note! This generates a lot of output, so if         
    238 #       you turn this on, be sure that the
    239 #       file defined in syslog.conf for LOG_NOTICE is a named pipe.
    240 #  You probably do not want this on.
    241 LOGSTATS off
    242 
    243 # Time interval in seconds between writing the DATA records to
    244 #   the log file. 0 disables.
    245 DATATIME 0
    246 
    247 # FACILITY defines the logging facility (class) for logging to syslog. 
    248 #          If not specified, it defaults to "daemon". This is useful 
    249 #          if you want to separate the data logged by apcupsd from other
    250 #          programs.
    251 #FACILITY DAEMON
    252 
    253 #
    254 # ========== Configuration statements used in updating the UPS EPROM =========
    255 #
    256 
    257 #
    258 # These statements are used only by apctest when choosing "Set EEPROM with conf
    259 # file values" from the EEPROM menu. THESE STATEMENTS HAVE NO EFFECT ON APCUPSD.
    260 #
    261 
    262 # UPS name, max 8 characters 
    263 #UPSNAME UPS_IDEN
    264 
    265 # Battery date - 8 characters
    266 #BATTDATE mm/dd/yy
    267 
    268 # Sensitivity to line voltage quality (H cause faster transfer to batteries)  
    269 # SENSITIVITY H M L        (default = H)
    270 #SENSITIVITY H
    271 
    272 # UPS delay after power return (seconds)
    273 # WAKEUP 000 060 180 300   (default = 0)
    274 #WAKEUP 60
    275 
    276 # UPS Grace period after request to power off (seconds)
    277 # SLEEP 020 180 300 600    (default = 20)
    278 #SLEEP 180
    279 
    280 # Low line voltage causing transfer to batteries
    281 # The permitted values depend on your model as defined by last letter 
    282 #  of FIRMWARE or APCMODEL. Some representative values are:
    283 #    D 106 103 100 097
    284 #    M 177 172 168 182
    285 #    A 092 090 088 086
    286 #    I 208 204 200 196     (default = 0 => not valid)
    287 #LOTRANSFER  208
    288 
    289 # High line voltage causing transfer to batteries
    290 # The permitted values depend on your model as defined by last letter 
    291 #  of FIRMWARE or APCMODEL. Some representative values are:
    292 #    D 127 130 133 136
    293 #    M 229 234 239 224
    294 #    A 108 110 112 114
    295 #    I 253 257 261 265     (default = 0 => not valid)
    296 #HITRANSFER 253
    297 
    298 # Battery charge needed to restore power
    299 # RETURNCHARGE 00 15 50 90 (default = 15)
    300 #RETURNCHARGE 15
    301 
    302 # Alarm delay 
    303 # 0 = zero delay after pwr fail, T = power fail + 30 sec, L = low battery, N = never
    304 # BEEPSTATE 0 T L N        (default = 0)
    305 #BEEPSTATE T
    306 
    307 # Low battery warning delay in minutes
    308 # LOWBATT 02 05 07 10      (default = 02)
    309 #LOWBATT 2
    310 
    311 # UPS Output voltage when running on batteries
    312 # The permitted values depend on your model as defined by last letter 
    313 #  of FIRMWARE or APCMODEL. Some representative values are:
    314 #    D 115
    315 #    M 208
    316 #    A 100
    317 #    I 230 240 220 225     (default = 0 => not valid)
    318 #OUTPUTVOLTS 230